    HV instrument transformers,Inductive Voltage Transformer, PT, SSVT, Oil or SF6 Gas Insulated, 36kV~550kV

    Inductive Voltage Transformer, VT, PT
    36kV…550kV JDX-, JDCF- series, Oil immersed
    36kV…550kV JDQXF-series, SF6 Gas insulated


    Station Service Voltage Transformer, SSVT
    Auxiliary Services Voltage Transformers
    Power Voltage Transformer
    36kV…550kV SSVT-series, Oil immersed

    36kV…550kV SSVT-series, SF6 Gas insulated

    500kV, 420kV, 362kV, 300kV, 245kV 170kV 145kV 123kV 72.5kV 52kV, 36kV High voltage Voltage transformer, potential transformer,high voltage inductive voltage transformer, station service voltage transformer PT, VT, IVT, SSVT

    JDX-, JDCF- series voltage transformer, outdoor, oil-immersed inductive type, single phase, hermetically sealed, earthed, cascade-type voltage transformer with high accuracy and protective class secondary windings. Used for metering and relay protection, applying to highland area.

    The voltage transformer consists of internal insulation parts, a porcelain insulator, oil, base, metallic bellows. The high-voltage windings are separated into two (or four) parts that are located on two poles of the core. The secondary windings are located in the lower pole of the down core. Three secondary windings are: metering, protective and residual windings. The core is designed to have low flux density. There is an oil drain plug in the base. A set of oil draining device is supplied for three transformers.

    Main Technical Parameter
    · Highest voltage for equipment: 36--550 kV
    · Power frequency: 50 or 60 Hz
    · Rated secondary voltage:110/√3V, 115/√3V, 120V
    · Rated secondary voltage for the earthing core: 100/3 V, 110/3 V or 100 V, 110V
    · Output of the metering class:5~400VA/CL0.2, 0.3, 0.5, 0.6
    · Output of the protection class:5~400VA/CL3P, 6P
    · Residual windings output:3P, 6P output: 400 VA
    · Ambient temperature: -50℃ to +50℃
    · Creepage distance: 25mm or 31mm/Kv
    · Partial discharge level: <10 pC

    Rated Insulated Level

    Type

    Highest system

    Voltage

    kV (r.m.s)

    Power frequency

    withstand voltage

    kV (r.m.s)

    lighting impulse

    test voltage

    kV (peak)

    JDX-72.572.5140325
    JDX -123123230550
    JDX -145145275650
    JDX -170170325750
    JDX -245245395950


    500kV 400kV 330kV 275kV 230kV 220kV 161kV 150kV 138kV 132kV 115kV 110kV 69kV 66kV 63kV 52kV 33kV High voltage oil immersed voltage transformer, potential voltage,high voltage inductive voltage transformer PT, VT, IVT, SSVT.

    Quality HV instrument transformers,Inductive Voltage Transformer, PT, SSVT, Oil or SF6 Gas Insulated, 36kV~550kV for sale
    Send your message to this supplier
     
    From:
    To: Hunan sandian electric co.ltd
    Subject:
    Message:
    Characters Remaining: (0/3000)
     
    Inquiry Cart 0

    Home| Products| Suppliers| Quality Suppliers| Site Map |About Us |Contact Us |Help |关于我们 |联系我们

    Copyright © 2009 - 2019 hfcletter.com. All rights reserved.